15KV, 220 MIL EPR/PVC 133%, T/S, W/G, ALUMINUM ARMOR (3/C)

SKU: 002

15kVU Type MV-105 or MC. 3 Copper Conductors. Thermosetting Conductor Shield. EPR Insulation. Thermosetting Insulation Shield. Tape Shield. Copper Ground Wire. Aluminum Armor. PVC Jacket.

APPLICATIONS

Southwire AL13ET Type MV-105 or MC Cable is for use in aerial installations, direct burial, concrete-encased installations, cable trays, troughs or continuous rigid cable supports. These cables are capable of operating continuously at a maximum conductor temperature of 105°C for normal operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions, and are rated at 15,000V, 133% insulation level (ungrounded system).

SPECIFICATIONS

Southwire AL13ET Type MV-105 or MC Cable is manufactured and tested in accordance with the latest revisions of the following standards and specification:

    • UL 1072 – Medium Voltage Power Cables.
    • ICEA S-93-639 (NEMA WC 74) – 5-46 kV Shielded Power Cable for Use in the Transmission & Distribution of Electric Energy.
    • IEEE 1202 – Flame Test (70,000 Btu/hr Vertical Tray Test).
    • ICEA T-29-520 – Vertical Cable Tray Flame Test (210,000 Btu/hr).

Certified qualification tests were performed in accordance with the requirements of AEIC CS-8. Cable has fully met the qualification testing requirments of AEIC CS-8.

 

CONSTRUCTION

Southwire AL13ET Type MV-105 or MC Cable offers heavy duty construction and flexible EPR insulation. Alternate constructions available. For use in cable trays per NEC Article 392. SOLONON™ low smoke, non halogen polyolefin jackets and CPE jackets are available upon request.

 

AL13ET 3c, 15kV, 220mil EPR(133%), TS, GW, Alum Interlocked

SCOPE: This specification covers three conductor EPR (ethylene propylene rubber) insulated, shielded, interlock armored, thermoplastic jacketed power cables with grounding conductor for use in aerial installations, direct burial, concrete-encased installations, cable trays, troughs, or continuous rigid cable supports. These cables are capable of operating continuously at a temperature of 105°C for normal operations, 140°C for emergency overload conditions, and 250°C for short circuit conditions, and are rated at 15,000V, 133% insulation level (ungrounded system).

STANDARDS: The following standards shall form part of this specification: UL Standard 1072 for Medium Voltage Power Cable and ICEA S-93-639 (NEMA WC 74) 5-46 kV Shielded Power Cable for Use in the Transmission and Distribution of Electric Energy.

CONDUCTOR: The conductor shall be Class B compressed concentric stranded bare copper in accordance with ASTM B3 and B8.

CONDUCTOR SHIELD: The conductor shall be shielded with an extruded semi-conducting thermosetting polymeric layer, which shall be firmly bonded to the insulation. The thickness shall be in accordance with the referenced standards.

INSULATION: The insulation shall be EPR (ethylene propylene rubber) meeting the requirements of the referenced standards. The nominal thickness shall be 0.220″.

INSULATION SHIELD: The insulation shall be shielded with an extruded semi-conducting thermosetting polymeric layer which shall be identified as semi-conducting. Over this layer shall be applied a helically-wrapped 5-mil copper tape with 25% overlap. The method of phase identification will be similar to ICEA Method 3, using printed circuit numbers and colors (1-BLACK, 2-RED, 3-BLUE).

GROUNDING CONDUCTOR: The ground conductor shall be Class B compressed concentric stranded bare copper in accordance with ASTM B3 and B8.

ASSEMBLY: The insulated and shielded power conductors shall be cabled round with fillers and with a grounding conductor in one outer interstice and covered with a binder tape.

ARMOR: A single strip of interlocked armor of aluminum shall be applied over the assembly.

JACKET: The cable shall be covered with a red PVC jacket conforming to the requirements specified for polyvinyl chloride in ICEA. The average thickness shall be in accordance with the referenced standards. The jacket will be sunlight resistant and will meet the requirements of UL 1685 – UL Flame Exposure Test. Optional SOLONON low smoke, non halogen polyolefin jackets and CPE jackets are available upon request.

IDENTIFICATION: Manufacturer’s identification shall be printed on the jacket.

TESTS: Qualification tests shall be conducted in accordance with the requirements of AEIC.

DON'T SEE WHAT YOU'RE LOOKING FOR?

sales@prolinesafety.com

(630) 876-1050

Pro-Line Safety Products Co. 1099 Atlantic Drive, Unit #1 West Chicago, IL 60185

Become A Distributor

We’re looking for qualified companies to join our distributor team!

©2022 Trident Solutions. All rights reserved. We are an equal opportunity employer and are dedicated to hiring qualified candidates.